    Monitor a PTO/Fuel Pump

    Learn how to effectively diagnose mechanical faults in a PTO/Fuel Pump system and keep it running optimally.

    Written by Matthew Clark-Massera

    Updated at December 12th, 2023

      Contact Us

      If you still have questions or prefer to get help directly from an agent, please submit a request.
      We’ll get back to you as soon as possible.

      Contact Support
      • Home
      • Device Features
      • Configuring I/Os

      Applies to:

      Device Firmware Version
      Dart3-2G and Dart3-4G All Versions
      G120-2G and G120-4G All Versions
      G70-2G and G70-4G All Versions

      The wired devices have Digital Inputs that can be used to monitor a secondary bit of equipment on an asset, i.e. sprayer, fuel pump, PTO.

      In most cases, we wire and configure the input in the same way as our dedicated ignition input (the white wire on the wired devices). 

      We consider the input 'on' when there is voltage present at the input (a high signal), and off when there is no voltage. 

      Dart3 Wiring

      The Dart3 has 3 x Digital Inputs (+1 dedicated Ignition Digital Input). 

      Connect the Dart3 ground wire (any black wire) to ground on our asset, and our chosen digital input wire to the high side of the pump/PTO etc.

      • Digital Input 1 = PINK
      • Digital Input 2 = BLUE
      • Digital Input 3* = GREEN

      *Digital Input 3 is shared with one of the Driver ID lines, so DI3 cannot be used at the same time as a DM RFID reader, or Wiegand Reader

      The Digital Input is considered on when above 2.2V, and off when below 0.8V.

       
       

      G120 Wiring

      The G120 has 6 digital inputs represented by the following coloured pins in the 24-wire harness.

      • Digital Input 1: Pin 16 - Pink
      • Digital Input 2: Pin 17 - Blue
      • Digital Input 3: Pin 18 -Green/Black
      • Digital Input 4: Pin 19 - Brown
      • Digital Input 5: Pin 4 - Brown/Blue
      • Digital Input 6: Pin 5 - Violet/Red

      Connect the G120 ground wire (any black wire) to ground on the asset, and the chosen digital input wire to the high side of the pump/PTO etc. G120 Harness Definition

      The Digital Input is considered ON when above 2.4V and OFF when below 2.0V

       
       

      G70 Wiring

      The G70 has 3 x Digital Inputs (+1 dedicated Ignition Digital Input).

      Connect the Dart3 ground wire (any black wire) to ground on our asset, and our chosen digital input wire to the high side of the pump/PTO etc.

      • Digital Input 1 = BLUE 
      • Digital Input 2 = ORANGE
      • Digital Input 3* = PURPLE

      *Digital Input 3 is shared with one of the Driver ID lines, so DI3 cannot be used at the same time as a DM RFID reader, or Wiegand Reader

      The Digital Input is considered on when above 2.2V, and off when below 0.8V.

       
       

      Parameters

      The configuration would be:

      • Bias resistor set to 'pull down'
        • When not running, there is no voltage present on the input. It is held low.
      • The Active Level is set to high
        • When running, there is a high voltage signal at the input.
        • The digital input is considered on. 
      • If we want to know in real-time if we are on or off, we should set Upload on Active and Upload on Inactive = Yes.

      Further Applications 

      Once we are tracking the status, we are able to enable further functionality:

      Secondary Run Hours (TG)

      We can track the hours that a Digital Input is active in Telematics Guru. See Setting up Secondary Run Hours.

       
       

      Asset State Configuration (TG)

      Depending on the state of the Digital Input, Telematics Guru can show the asset as a different colour in the Live View and Trip History View, i.e. spraying is occurring. See Asset State Configuration

       
       

      Configure Alerts and Run Reports (TG)

      Events and Alerts may be used to setup reports on Telematics Guru. See guide here - Events vs Alerts. 

       
       

      Input Monitor

      Create alerts based on the status of multiple inputs - Input Monitor

       
       
      fuel pump pto monitor

      Was this article helpful?

      Yes
      No
      Give feedback about this article

      Related Articles

      • Digital Inputs Introduction
      • Set Up A Panic/Duress Button
      • Input Monitor
      • Connect an External Buzzer/LED

      Subscribe to Partner News

      Subscribe to our mailing list to receive Digital Matter news, product and tehnical updates, and more.

      Subscribe

      Copyright © Digital Matter . All Rights Reserved.

      Privacy Contact Support

      Knowledge Base Software powered by Helpjuice

      DM Logo
      Expand