Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Digital Matter Site
  • Contact Us

Hawk - Configure T9602 Temperature Probe

Written by Matthew Clark-Massera

Updated at October 6th, 2023

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Contact Support
  • Home
  • Devices
  • Cellular
  • Data Loggers
  • Hawk IoT Datalogger
  • I²C

Table of Contents

Related Articles 3rd Party Sensor Selecting Sensor IO Card Wiring Parameters I²C Action Parameters Task Parameters Output/Conversion

Related Articles

Please ensure to also read the below for full details on configuring Tasks and I²C Sensors for the Hawk

  • Hawk Operation - Task Schedules
  • Configure I²C Sensor Readings
 

The T9602 is an IP67 rated Temperature + Humidity Sensor which can be used with the Hawk for temp+hum monitoring applications

3rd Party Sensor

The T9602 is a 3rd Party sensor - the advice given below is general. Always check the product datasheet direct from the manufacturer. Specific guidance on installation and usage should be obtained directly from the manufacturer. The instructions below are based on a sensor tested at the time of article writing - things may change.

 

Selecting Sensor

There are many T9602 variants. Ensure to select one which operates on 3V3, and not 5V

Mouser Link

IO Card

Ensure a plug-in IO card with an I²C interface is fitted to the Hawk. Currently the only card with this interface is the AgTech1 card.

Wiring

T9602 Agtech1 Bluetooth+
3V3 Hawk IO 5 Hawk IO 7
SCL Hawk IO 6 Hawk IO 5
SDA Hawk IO 4 Hawk IO 6
GND Hawk GND Hawk GND

Parameters

I²C Action Parameters

  1. Select T9602 as the Sensor Type
  2. Choose an Analogue to write the values to.
    1. Temp will be written to analogue offset
    2. Hum to analogue offset + 1
    3. In the example below this would be Temp in Analogue 15, and Humidity in Analogue 16

The I²C address can be left blank. For reference address 80 (0x50) is polled when taking a reading.

Task Parameters

Ensure the I²C action you have configured above (Action 1 or 2) is set as an action of the task.

Output/Conversion

With the above parameters, the output would be:

Value Analogue Units Conversion Example
Temperature Analogue Offset Value °C * 100 800 = 8°C
Humidity Analogue Offset Value + 1 % * 100 5000 = 50%
t9602 temp configure probe

Was this article helpful?

Yes
No
Give feedback about this article

Related Articles

  • Hawk - Configure DM Ambient (Temp+Hum Sensor)
  • Hawk - Configure MaxBotix MB7040 I²C Ultrasonic Range Sensor
  • Configure I²C Sensor Readings
  • Hawk - Configure DM Temp Probe (Deprecated)

Subscribe to Partner News

Subscribe to our mailing list to receive Digital Matter news, product and tehnical updates, and more.

Subscribe

Copyright © Digital Matter . All Rights Reserved.

Privacy Contact Support

Knowledge Base Software powered by Helpjuice

Expand